LIHHQH

Place of use

This type of cables are used as signal and data transmission cables in the connections of electronic control systems, sound frequency transmission. This type of cables is halogen-free, has flame -retarder and low smoke density. The armor on cable protects it agaınst mechanical impacts.

Structure

Inner Conductor

Electrolytic Stranded Annealed Copper Wire, Class 5
EN 60228, IEC 60228, VDE 0295

Insulation

HFFR Compound EN 50290-2-26, DIN 47100 Colour Code

Stranding

Cores Twisted in Layers

Seperator

PES Tape

Inner Sheath

HFFR Compound EN 50290-2-27, RAL 7001 Grey

Armour

Galvanized  Steel Wire Braiding

Outer Sheath

HFFR Compound EN 50290-2-27, RAL 7001 Grey

 

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C

Technical Info


CONDUCTOR
RESISTANCE

INSULATION
RESISTANCE

CAPACITANCE

CURRENT CARRYING
CAPACITY

OPERATING
VOLTAGE

TEST
VOLTAGE

BENDING
RADIUS

TEMPERATURE
RANGE

 
 

mm²

Ω/km

MΩxKm

mm²

pf/m

mm²

A

300/500 V

1500V

7,5XD

-30ºC +70ºC

 

0.22

88

≥ 200

0.22

100

0.22

2.5

 

0.34

56

0.34

110

0.34

4.5

 

0.50

39

0.50

120

0.50

6

 

0.75

26

0.75

120

0.75

13

 

1.00

19.5

1.00

130

1.00

16

 

1.50

13.3

1.50

140

1.50

20

 

2.50

7.98

2.50

150

2.50

25

 
                               

FLAME RETARDANT TEST

SMOKE DENSITY TEST

TEST ON CORROSIVENESS
OF COMBUSTION GASES

HALOGEN
FREE TEST

FLAME
RETARDANT
TEST

   
   

IEC 60332-1-2                         VDE 0482-332-1-2           EN 60332-1-2

IEC 61034-2
VDE 0482-1034-2
EN 61034-2

IEC 60754-2                     VDE 0482-267-2-3             EN 50267-2-3

IEC 60754-1            VDE 0482-267-2-1              EN 50267-2-1

IEC 60332-3-24                     VDE 0482-332-3-24                  EN 60332-3-24

   
   
   
                             

 


Catalog Info